Electro Industries Shark 200 Installation & Operation Manual page 43

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Fault Withstand:
Reading:
Current Inputs
(For Accuracy specifications, see 2.4: Accuracy on page 2-19.)
Class 10:
Class 2:
Burden:
Pickup Current:
Connections:
Fault Withstand (at 23
Reading:
Continuous Current Withstand:
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
o
C):
Doc
2: Meter Overview and Specifications
Meets IEEE C37.90.1
Programmable Full Scale to any PT
ratio
5 A Nominal, 10 A Maximum
1 A Nominal, 2 A Maximum
0.005 VA Per Phase Max at 11 A
0.1% of Nominal (0.2% of Nominal
if using Current Only mode, that is,
there is no connection to the
voltage inputs)
O Lug or U Lug electrical connec-
tion (Figure 4.1)
Pass through wire, 0.177" / 4.5 mm
maximum diameter (Figure 4.2)
Quick connect, 0.25" male tab
(Figure 4.3)
100 A/10 s, 300 A/3 s, 500 A/1 s
Programmable Full Scale to any CT
ratio
20 A for screw terminated or
pass through connections
#
E149701
2-13