Electro Industries Shark 200 Installation & Operation Manual page 342

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

</Communication>
The node <P type="IP" xsi:type="tP_IP"> (bolded in the example above) defines the
meter's IP address. This IP address must be the same as the IP address configured in
the meter's Device Profile (see step 4 in Section E.4.1) for each IEC 61850 Protocol
Ethernet Network card in the meter.
Also, make sure that the iedName field in the ConnectedAp section (underlined in the
example) is the same as the name field defined in the IED section.
This is how the unit is assigned its name and IP address.
1. The Shark® 200 meter's .icd file can be downloaded directly from the Shark® 200
unit. To do this, use a web browser and enter:
http://aa.bb.cc.dd/
, where aa.bb.cc.dd is the IP address assigned to the IEC 61850 Protocol Ethernet
Network card (see E.2.3: Configuring the IEC 61850 Protocol Ethernet Network
Card on page E-15).
The Information webpage is displayed.
NOTE: The firmware runtime version which is displayed in the Run Ver field of this
webpage determines the default password for Network card upgrading, uploading
the .cid file, and resetting the Network card.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
E: Using the IEC61850 Network Card
#
Doc
E149701
Firmware
Runtime
Version
E-22

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents