Load Bar Custom Configuration; Enable Fixed Scale For Voltage Display - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Load Bar Custom Configuration: To enter scaling for the Load Bar, click the Load
Bar Custom Configuration checkbox. Fields display on the screen that allow you to
enter a Scaling factor for the display. See the figure below.
Enter the scaling factor you want in the Current Scale field. This field is multiplied by
the CT Multiplier (set in the CT, PT Ratios, and System Hookup screen) to arrive at the
Primary Full Scale. Make sure you set the CT multiplier correctly.
Enable Fixed Scale for Voltage Display: To enter a scaling factor for the Voltage
display, click the checkbox next to Enable Fixed Scale for Voltage Display. The screen
changes - see the figure below.
Select the scaling you want to use from the pull-down menu. The options are: 0,
100.0 kV, 10.00 kV, or 0 kV.
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
5: Communication Installation
#
Doc
E149701
5-20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents