Dnp Object Point Map; Binary Input Status With Flags; Supported Flags - Electro Industries Shark 200 Installation & Operation Manual

Upgradeable fully featured power & energy meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

C.7: DNP Object Point Map
Object 1 - Binary Input Status with Flags
Read with Object 1, Var 2, and Qualifiers 0, 1, 2 or 6. (Included in Class 0 responses.)
Object
Point
Var
1
0
2
1
1
2
1
2
2
1
3
2

Supported Flags:

Bit 0: ONLINE (0=Offline, 1=Online) (If the Input is not present it will be shown as
Offline.)
Bit 1: RESTART (1=The Object is in the Initial State and has not been updated since
Restart.)
Bit 7: STATE (0=Off, 1=On)
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Description
Format
BYTE
Read Digital Input
1 RO1S Status 1
(expansion port 1)
BYTE
Read Digital Input
2 RO1S Status 2
(expansion port 1)
BYTE
Read Digital Input
3 RO1S Status 1
(expansion port 2)
BYTE
Read Digital Input
4 RO1S Status 2
(expansion port 2)
C: DNP Mapping
Range
Multiplier
Units
Bit Flags
None
N/A
Bit Flags
None
N/A
Bit Flags
None
N/A
Bit Flags
None
N/A
#
Doc
E149701
Comments
Returns the Status
and State of the
Input in the Flags.
Returns the Status
and State of the
Input in the Flags.
Returns the Status
and State of the
Input in the Flags.
Returns the Status
and State of the
Input in the Flags.
C-6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 200t

Table of Contents