Siemens SIMOVERT MASTERDRIVES Manual page 68

Motion control
Hide thumbs Also See for SIMOVERT MASTERDRIVES:
Table of Contents

Advertisement

Instructions for Design of Drives in Conformance with EMC Regulations
Example of correct
cable routing
Cable duct only for line supply cables
Shielded motor cables
3-24
Cable duct only for
signal cables
Fig. 3-19
Installation with separate cable ducts
Installation with cable ducts only for the line supply cables. Line supply
cables are non-shielded.
The motor and signal cables are routed separately from each other.
The shields of the motor and signal cables have to be mounted on the
shield connections through the largest possible surface area.
6SE7087-6QX70 (Version AD)
Compendium Motion Control
05.2003
Siemens AG
SIMOVERT MASTERDRIVES