Siemens SIMOVERT MASTERDRIVES Manual page 393

Motion control
Hide thumbs Also See for SIMOVERT MASTERDRIVES:
Table of Contents

Advertisement

Communication / PROFIBUS
8.2.9.7
Communication interface
Node address
8.2.9.8
Clock synchronous application
Pos Controller
clock time
(T
)
MAPC
Master
R1
R2
DP cycle
T S1 S2 S3 MSG
Speed/current
controller clock
time
T
SAPC
R1
Slave 1...3
T
= 0
I
8.2-106
P918: Node address
Value range 0 – 125 (126 is reserved for start-up purposes)
The node addresses 0, 1 and 2 are generally occupied by master
and configuration tools and therefore should not be used for
slaves on the PROFIBUS. Address 3 is the first appropriate node
address to be used for a slave on the PROFIBUS.
Course of an isochronous DP cycle
Example (simplest DP cycle, standard case for MASTERDRIVES)
R3
R1
R2
Reserve
T
S1 S2 S3 MSG
R1
R1
R1
R1
R1
Fig. 8.2-37
Example: simplest DP cycle
In this example four DP cycles are needed for a response in the position
control circuit.
♦ 1. Actual value recording
♦ 2. Actual value transmission (slave -> master)
♦ 3. Position controller
♦ 4. Setpoint transmission
This model makes few demands on the computing output of the master,
but leads to an increase in the control-specific dead time:
Dead time = 4 * T
DP
T
= 0
M
R3
R1
R2
R3
Reserve
T
S1 S2 S3 MSG
R1
R1
R1
R1
(in slave)
(in master)
(master -> slave)
.
6SE7087-6QX70 (Version AG)
Compendium Motion Control
R1
R2
R3
Reserve
T
S1 S2 S3 MSG
R1
R1
R1
R1
R1
Siemens AG
SIMOVERT MASTERDRIVES
05.2006
Reserve
T
R1
R1
T
= 0
O