Communication / PROFIBUS
Example
Bit No.:
15
1
8.2-20
Reply ID
0
No reply
1
Transfer parameter value (word)
2
Transfer parameter value (double word)
Transfer description element 1
3
Transfer parameter value (array, word) 2
4
Transfer parameter value (array, double word) 2
5
6
Transfer the number of array elements
7
Task cannot be executed (with error number)
8
No operator change rights for the PKW interface
9
Parameter change report (word)
10
Parameter change report (double word)
Parameter change report (array, word) 2
11
Parameter change report (array, double word) 2
12
13
Reserved
14
Reserved
15
Transfer text (not with CBP)
1
The required element of the parameter description is specified in IND (2nd word)
2
The required element of the indexed parameter is specified in IND (2nd word)
Table 8.2-5
Reply IDs (converter -> master)
Source for the ON/OFF1 command (control word 1, bit 0):
P554 (=22A Hex)
Change parameter value (array, word) and store in the EEPROM
Parameter ID
12
11
10
AK
SPM
1
0
0
0
0 1 0
C
2
♦ Bits 12 to 15: Value = 12 (= "C" Hex); change parameter value (array,
word) and store in the EEPROM
♦ Bits 0 to 11: Value = 554 (= "22A" Hex); parameter number without
set bit for the parameter change report
Significance
(PKE)
PNU
0 0 1 0
2
6SE7087-6QX70 (Version AG)
Compendium Motion Control
st
1
word
0
1
0
1 0
Binary value
A
HEX value
Siemens AG
SIMOVERT MASTERDRIVES
05.2006