Parameterizing Steps
SLB inserted ?
no
yes
P740 = ?
P741 = ?
P742 = ?
P740 > 0
P740 = 0
P743 = ?
P745 = ?
P746 = ?
P749.1...8 = ?
CBx inserted ?
no
P918.1...2 = ?
P060 = 1
6-12
Enter the SLB module address
0:
greater than 0:
Enter the SLB telegram failure time in ms
0:
greater than 0:
Enter the SLB transmit power (for plastic fiber-optic cables)
1: weak
up to 15 m fiber-optic cable length
2: medium up to 25 m fiber-optic cable length
3: strong
up to 40 m fiber-optic cable length
NOTE:
If glass fiber-optic cables are used, the possible
lengths are increased by the factor 7.5.
Enter the number of modules (incl. dispatcher)
in the SIMOLINK ring
Enter the number of channels per module
Enter the SIMOLINK cycle time in ms
Enter the SLB read addresses
yes
Enter the CB bus addresses
Return to the parameter menu
Unit operates as a dispatcher
Unit operates as a transceiver
No monitoring
Monitoring time in ms
6SE7087-6QX70 (Version AH)
Compendium Motion Control
02.2007
Siemens AG
SIMOVERT MASTERDRIVES