Table 8.1-6
Reply IDs (drive converter -> master)
Source for the ON/OFF1 command (control word1, bit 0):
P554 (=22A hex) Change parameter value (array, word) and save in
the EEPROM.
Parameter ID (PKE)
12
11
10
AK
SPM
1
0
0
0
0 1 0
C
2
♦ Bits 12 to 15: Value = 12 (= "C" hex); change parameter value (array, word) and save
in the EEPROM
♦ Bits 0 to 11: Value = 554 (= "22A" hex); parameter number with a set change-report
bit
Compendium Motion Control
Meaning
No reply
Transfer parameter value (word)
Transfer parameter value (double word)
Transfer descriptive element
Transfer parameter value (array, word)
Transfer parameter value (array, double word)
Transfer the number of array elements
Task cannot be executed (with error number)
No control/change rights for the PKW interface
Parameter change report (word)
Parameter change report (double word)
Parameter change report (array, word)
Parameter change report (array, double word)
Reserved
Reserved
Transfer text