Automation Direct DURApulse GS4 User Manual page 98

Hide thumbs Also See for DURApulse GS4:
Table of Contents

Advertisement

Chapter 4: AC Drive Parameters
v/h
P
z
araMeters
For detailed information about the P2.xx parameter group, please refer to
Parameter
1) ♦ in the Run-Read/Write column indicates that the parameter can be set during RUN mode.
R/W indicates "read/write. "
Read indicates "read-only. "
2) Parameters can be restored to their default values using P9.08.
P2.00
Volts/Hertz Settings
P2.01
Slip Compensation Gain
P2.02
Torque Compensation Gain
P2.03
Torque Compensation Filter
P2.04
Motor 1 Middle Output Frequency 1 0�00~600�00 Hz
P2.05
Motor 1 Middle Output Voltage 1
P2.06
Motor 1 Middle Output Frequency 2 0�00~600�00 Hz
P2.07
Motor 1 Middle Output Voltage 2
P2.08
Motor 1 Minimum Output Frequency 0�00~599�99 Hz
P2.09
Motor 1 Minimum Output Voltage
PWM Carrier Frequency
N
: t
ote
here are iNterdepeNdeNcies
P2.10
p2.10, p6.00/p6.02, p6.33,
betweeN
p6.34. r
efer to
wheN settiNg these parameters
P2.11
Control Mode
P2.12
Motor 2 Middle Output Frequency 1 0�00~600�00 Hz
P2.13
Motor 2 Middle Output Voltage 1
P2.14
Motor 2 Middle Output Frequency 2 0�00~600�00 Hz
Page 4–4
s
(P2.
)
uMMary
xx
GS4 Parameters Summary – V/Hz Parameters (P2.xx)
Range
0: General Purpose
1: High Starting Torque
(TQR)
2: Fans and Pumps
3: Custom
4: 1�5 Power Curve
5: Square Curve
0�00~10�00
0~10
0�001~10�000 sec
230V: 0�0~240�0V
460V: 0�0~480�0V
230V: 0�0~240�0V
460V: 0�0~480�0V
23 0V: 0�0~240�0V
46 0V: 0�0~480�0V
2~15 kHz
p
d
arameter
etails
.
0: V/Hz Open Loop Control
1: SVC Sensorless
230V: 0�0~240�0V
460V: 0�0~480�0V
(table continued next page)
DURA
pulse
Modbus
Run
1)
Address
Read/
Write
Hex
R/W
0200 40513 0
♦R/W
0201 40514
♦R/W
0202 40515 0
♦R/W
0203 40516 0�5
R/W
0204 40517 3�00
♦R/W
0205 40518
R/W
0206 40519 3�00
♦R/W
0207 40520
R/W
0208 40521 1�50
♦R/W
0209 40522
R/W
020A 40523
♦R/W
020B 40524 0
R/W
020C 40525 3�00
♦R/W
020D 40526
R/W
020E
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
page
4–49.
Settings
2)
Dec
Default
0� 00
(V/Hz mode)
1� 00
(Vector mode)
G S4-
21P0~27P5: 15�0V
2010+: 14�0V
G S4-
41P0~47P5: 30�0V
4010+: 28�0V
G S4-
21P0~27P5: 15�0V
2010+: 14�0V
G S4-
41P0~47P5: 30�0V
4010+: 28�0V
G S4-
21P0~27P5: 9�0V
2010+: 7�0V
G S4-
41P0~47P5: 18�0V
4010+: 14�0V
model specific; refer
to param� details
G S4-
21P0~27P5: 15�0V
2010+: 14�0V
G S4-
41P0~47P5: 30�0V
4010+: 28�0V
40527 3�00
User