Chapter 6: Maintenance and Troubleshooting
Display on GS4-KPD Keypad
Warning
ECto
ExCom Inr T-out
Warning
ECCS
ExCom Inr CRC
Warning
ECrF
ExCom Rtn def
Warning
ECo0
ExCom MTCP over
Warning
ECo1
ExCom EIP over
Warning
ECiP
ExCom IP fail
n/a
Warning
ECbY
ExCom Busy
Warning
ECCb
ExCom Card brk
Page 6–14
Warning Codes (continued)
Warning
Code in
2108h
Descriptions
Active
Warning
LOCAL
81
Communication time-out for communication card and drive
LOCAL
82
Check sum error for communication card and drive
LOCAL
83
Communication card returns to default setting
LOCAL
84
Modbus TCP exceeded maximum communication value
LOCAL
85
EtherNet/IP exceeded maximum communication value
LOCAL
86
IP fail
87
reserved
LOCAL
88
Communication card busy
LOCAL
Loss of communication between Communication Card and GS4 drive�
To recover:
89
Power down the drive and remove all communication cables� Remove and re-
seat the comm card� Do not reconnect any comm cables� Power up the drive� If
the ECCb fault still exists, replace the comm card�
(continued next page)
DuRA
pulse
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Need help?
Do you have a question about the DURApulse GS4 and is the answer not in the manual?