Fault Name
LOCAL
Fault
FStp
PLC Force Stop
n/a
LOCAL
Fault
CD10
Card TimeOut
n/a
LOCAL
Fault
TRAP
CPU Command Err
n/a
DuRA
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
pulse
Chapter 6: Maintenance and Troubleshooting
Fault Code
Fault
in Status
Descriptions
Monitor 1
If the GS4 drive is running in PLC mode, parameter P3�00 is equal to
1, 3 or 5, and Remote Operation is selected; or parameter P3�01 is
90
equal to 1, 3, or 5, and Local operation is selected, the drive can be
forced to stop by pressing the STOP key on the keypad�
91~96
reserved
Ethernet
communication
has not been
received from the
97
external controller
(within the
Ethernet Timeout
window)�
98
reserved
99
CPU trap error
100~111
reserved
Corrective Actions
n/a
Initiate Ethernet communications from the
master controller again, or Disable checking for
Ethernet Timeout in P9�94�
n/a
Should a CPU Trap error fault persist, please
send the drive back to the factory for evaluation�
n/a
Can be
Bypassed
in Fire
Mode
(Yes / no)
no
n/a
n/a
no
n/a
Page 6–25