Appendix E: Safe Torque Off

stl1 P6.71=1, P6.29=0

RUN command
STO1~SCM1
STO2~SCM2
Driveoutput
DrivePower

stl2 P6.71=1, P6.29=1

RUN command
STO1~SCM1
STO2~SCM2
Driveoutput
DrivePower
e
C
rror
oDeS for
P11.04
First Fault Record
P11.05
Second Most Recent Fault Record
P11.06
Third Most Recent Fault Record
P11.07
Fourth Most Recent Fault Record
P11.08
Fifth Most Recent Fault Record
P11.09
Sixth Most Recent Fault Record
Error Codes Pertaining to STO Function
72: STL1 STO1~SCM1 internal hardware detect error
76: STO Safety Torque Off function active
77: STL2 STO2~SCM2 internal hardware detect error
78: STL3 STO1~SCM1 and STO2~SCM2 internal hardware detect error
Page E–6
RUN
ON
OFF ON
status
ON
status
OutputStop
Operating
Reset
RUN
ON
status
ON
OFF ON
status
OutputStop
Operating
Reset
Sto f
unCtion
DuRA
pulse
STOP
RUN
STOP
RUN
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
Operating
Operating
Type
Hex Addr
Dec Addr
Read
0B04
42821
Read
0B05
42822
Read
0B06
42823
Read
0B07
42824
Read
0B08
42825
Read
0B09
42826
Default