Chapter 4: AC Drive Parameters
a
i
nalog
nPut
This example illustrates the use of an inverse analog speed reference to the drive. The minimum
analog reference value corresponds to the full forward output frequency of the drive.
• Minimum Frequency Reference = 60Hz
• Maximum Frequency Reference = 0Hz
For AI1, AI2, and AI3: P4.24 (AI V/Hz Calculated Selection) MUST BE SET TO ZERO (All Inputs
Use Bias and Gain) TO ENABLE BIAS AND GAIN CALCULATIONS.
Calculations (see
A) Drive Maximum Output Frequency = P0.04 = (1750 rpm / 1750 rpm) x 60Hz = 60Hz
B) Analog Offset % = [(-60Hz) / (60Hz - 0Hz)] x 100 = -100%
Analog Input (AIx)
AIx Bias Parameter
C) Analog Gain % = [(60Hz - 0Hz) / 60Hz] x 100 = 100% = AIx Input Gain
Analog Input
Polarity
AIx Gain Parameter
D) Mid-point Frequency = [(60Hz - 0Hz) / 2] + 0Hz = 30Hz
Parameter Settings
Analog Input
Polarity
AIx Bias Parameter
AIx Polarity Parameter
AIx Gain Parameter
Reverse Run Parameter
Drive Max Output Freq
Results
Page 4–122
P
e
10: i
araMeter
xaMPle
page 4–112
for formulas)
AI1
P4�10
AI1
Positive (+)
P4�12
AI1 or
Positive (+)
Positive (+)
P4�10
P4�11
P4�12
Maximum
Output
Frequency
DURA
a
s
r
nverse
nalog
Peed
eFerence
AI2
AI3
P4�15
P4�19
AI2
Positive (+)
Positive (+)
P4�17
P4�21
AI2 or
AI3
Positive (+)
Negative (-)
P4�15
P4�19
P4�16
P4�20
P4�17
P4�21
P4�09
P0�04
60Hz
30Hz
0Hz
0V
5V
-10V
0V
0mA
10mA
4mA
12mA
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
pulse
AI3
Negative (-)
P4�22
Parameter Settings
-100�0%
1: Positive Offset
P4�22
100�0%
0: Digital FWD/REV
60Hz
10V
10V
20mA
20mA