When AI1 Voltage/Current Selection (P4.05) is voltage, the setting range of P4.25, P4.27, and P4.29
have to be 0.00~10.00 or 0.00~20.00.
When AI2 Voltage/Current Selection (P4.06) is voltage, the setting range of P4.31, P4.33, and P4.35
have to be 0.00~10.00 or 0.00~20.00. (Ex: If AI2 is set for 0~10V input, do not use 4~20mA settings
to calculate Low/Mid/High Points.)
The analog input values can be set at P4.25~P4.42, and the Maximum Operating Frequency can be
set at P0.04.
P4.24 must be set to use Low/Mid/High Point customization.
The corresponding functions of open-loop control are shown as images below.
High Point %
Mid Point %
Low Point %
DURA
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
pulse
Frequency
P0.04
P4.30
P4.36
P4.42
P4.28
P4.34
P4.40
P4.26
P4.32
P4.38
P4.25
P4.31
P4.37
Low-Point
Voltage
-AI3 Low Volts
-AI3 Mid Volts
-10V
Chapter 4: AC Drive Parameters
P4.27
P4.29
P4.33
P4.35
P4.39
P4.41
Mid-Point
High-Point
Voltage
Voltage
-AI3 High Volts
-5V
0V
0%
-AI3 High %
-50%
-AI3 Mid%
-100%
-AI3 Low%
Analog Input
20mA/10V
Page 4–105