This example illustrates the default operation of the drive. The example is given to further
illustrate the use of the analog calculations. The full range of the analog input signal corresponds
to the full forward frequency range of the AC drive.
• Minimum Frequency Reference = 0Hz
• Maximum Frequency Reference = 60 Hz
For AI1, AI2, and AI3: P4.24 (AI V/Hz Calculated Selection) MUST BE SET TO ZERO (All Inputs
Use Bias and Gain) TO ENABLE BIAS AND GAIN CALCULATIONS.
Calculations (see
A) Drive Maximum Output Frequency = P0.04 = (1750 rpm / 1750 rpm) x 60Hz = 60Hz
B) Analog Offset % = ( 0Hz / 60Hz ) x 100 = 0%
Analog Input (AIx)
AIx Bias Parameter
C) Analog Gain % = [(60Hz - 0Hz) / 60Hz] x 100 = 100% = AIx Input Gain
Analog Input
Polarity
AIx Gain Parameter
D) Mid-point Frequency = [(60Hz - 0Hz) / 2] + 0Hz = 30Hz
Parameter Settings
Analog Input
Polarity
AIx Bias Parameter
AIx Polarity Parameter
AIx Gain Parameter
Reverse Run Parameter
Drive Max Output Freq
Results
DURA
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
pulse
e
1: s
xaMPle
tandard
page 4–112
for formulas)
AI1
AI2
P4�10
P4�15
AI1
Positive (+)
Positive (+)
P4�12
AI1 or
AI2 or
Positive (+)
Positive (+)
P4�10
P4�15
P4�11
P4�16
P4�12
P4�17
Maximum
Output
60Hz
Frequency
30Hz
Chapter 4: AC Drive Parameters
o
Peration
AI3
P4�19
AI2
AI3
Positive (+)
Negative (-)
P4�17
P4�21
AI3
Positive (+)
Negative (-)
P4�19
P4�20
P4�21
P4�22
P4�09
P0�04
0Hz
0V
5V
10V
-10V
0V
10V
0mA
10mA
20mA
4mA
12mA
20mA
P4�22
Parameter Settings
0�0%
0: No Offset
100�0%
0: Digital FWD/REV
60Hz
Page 4–113