a
i
P
nalog
nPut
araMeter
This example gives 0Hz output through the first 0V~2.5V of Analog Input. The rest of the 2.5V~10V
corresponds to 0~45 Hz
• Minimum Frequency Reference = 0Hz
• Maximum Frequency Reference = 45Hz
Results
60Hz
45Hz
30Hz
15Hz
0Hz
-15Hz
0V
2.5V
-10V -5V
0mA 5mA 10mA
4mA 8mA 12mA
NOTE: Due to the way Bias, Gain, and Reverse works, the graph above cannot be achieved with the
Bias and Gain settings: If Reverse is enabled (P4.09), the motor will run reverse when the signal goes
below 2.5V. If reverse is disabled, the analog value will be evaluated as an absolute value (what would
have been negative motion will now result in positive motion).
S
P4.24
et
to uSe
B
g
). u
iaS and
ain
• Low Point = 0V input; 0Hz output; chart coordinates 0,0
• Mid Point = 2�5V input; 0Hz output; chart coordinates 2�5,0
• High Point = 10V input; 45Hz output; chart coordinates 10,45
NOTE: The Low/Mid/High Point method uses % output, instead of Hz. Therefore, the High Point value
in this example = 45Hz / 60Hz Max Output = 75%.
Parameter Settings
Analog Input
Polarity
AI V/Hz Calculated
Selection
AIx Low V/A
AIx Low Hz Percent
AIx Mid V/A
AIx Mid Hz Percent
AIx High V/A
AIx High Hz Percent
Reverse Run Parameter
DURA
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
pulse
e
9: z
xaMPle
ero
Output Frequency
FORWARD
The drive will not reverse direction unless the Frequency Command
is from an analog input, and reverse motion is enabled in P4.09.
5V
10V
0V
10V
20mA
20mA
L
P
, M
P
,
ow
oint
id
oint
and
Se tHe foLLowing SettingS to create a deadBand froM
AI1 or
AI2 or
Positive (+)
Positive (+)
P4�24 =
P4�24 =
1, 3, 5, or 7
2, 3, 6, or 7
P4�25
P4�31
P4�26
P4�32
P4�27
P4�33
P4�28
P4�34
P4�29
P4�35
P4�30
P4�36
Chapter 4: AC Drive Parameters
v
o
l
v
olts
ut at
ow
in
H
P
igH
oint SettingS for anaLog inPut conditioning
AI3
Positive (+)
Negative (-)
P4�24 = 4, 5, 6, or 7
P4�37
P4�43
P4�38
P4�44
P4�39
P4�45
P4�40
P4�46
P4�41
P4�47
P4�42
P4�48
P4�09
(
inStead of
0~2.5V
:
anaLog inPut
Parameter Settings
as shown to left, or
7: All Custom V/Hz
0V
0%
2�5V
0%
10V
75%
0: Digital FWD/REV
Page 4–121