Fault Name
LOCAL
Fault
ydc
Y-Delta Connect
LOCAL
Fault
dEb
DEB Error
LOCAL
Fault
oSL
Over Slip Error
LOCAL
Fault
ryF
Emag SwitchError
n/a
LOCAL
Fault
STL1
STO Loss 1
LOCAL
Fault
S1
ES1 E-Stop
LOCAL
Fault
Fire
In Fire Mode
n/a
LOCAL
Fault
STO
STO
DuRA
GS4 AC Drive User Manual – 1st Ed, Rev A - 10/20/2017
pulse
Chapter 6: Maintenance and Troubleshooting
Fault Code
Fault
in Status
Descriptions
Monitor 1
Y-connection/Δ-
61
connection switch
error
When P6�61 is
not set to 0 and
momentary power
62
is turned off, it will
display dEb during
accel/decel stop�
It will be displayed
when slip exceeds
63
P2�26 setting and
time exceeds P2�27
setting�
Electric valve
switch error when
executing Soft
Start�
64
(This warning is
for frames E and
higher frame of
GS4 drives)
65~71
reserved
72
STL1
Emergency stop
73
for external safety
74
In Fire mode
75
reserved
76
STO
(continued next page)
Corrective Actions
1) Check the wiring of the Y-connection/Δ-
connection.
2) Check the parameters settings.
1) Set P6.61 to 0.
2) Check if input power is stable.
1) Check if motor parameter is correct (please
decrease the load if overload).
2) Check the settings of P2.26 and P2.27.
Do not disconnect RST when drive is still
operating�
n/a
STO1~SCM1 internal hardware detect error�
(See Appendix E for corrective action�)
Fault S1 is generated upon a loss of the E-Stop
input at ES1�
The corrective action is to restore the E-Stop
input to the drive at ES1�
Fire fault is due to the multi-function input set
as 40 or 41 and that DI is ON�
For some installations, particularly exhaust fan
operation where smoke is detected and requires
evacuation, it is highly desired for the drive to
run the fan as long as is needed to exhaust that
smoke�
n/a
Safety Torque Off function active�
(See appendix E for corrective action�)
If unknown STO faults occur, the onboard +24V
might be getting shorted (+24V to DCM)�
Can be
Bypassed
in Fire
Mode
(Yes / no)
no
no
no
no
n/a
no
no
Yes
n/a
no
Page 6–23