Remove and Install Filler Panels

Remove and Install Filler Panels
See the procedures in the following table to remove and install filler panels for
storage drives and PCIe cards.
Filler Panel
Type
Storage Drive
PCI Slot

Install the Server Top Cover

1.
Open the server fan door.
See
"Open the Server Fan Door" on page
Place the top cover on the chassis [1].
2.
Place the cover down so that it hangs over the rear of the server by about 13 mm (0.5 inches)
and the side latches align with the slots in the sides of the chassis.
Note -
the left side (viewing the server from the front). There is also a latch on the underside of the
cover in the front left corner.
188
Oracle Server X6-2 Service Manual • June 2016
Removal Procedure
1. Locate the storage drive filler panel to be
removed from the server.
2. To unlatch the storage drive filler panel, pull
the release lever, and then tilt the lever out
into a fully opened position.
3. To remove the filler panel from the slot, hold
the opened release lever, and gently slide the
filler panel toward you.
1. Remove the server top cover.
2. To remove the PCIe slot filler panel, rotate
the PCIe locking mechanism, and then lift
and remove the PCIe slot filler panel from the
location into which you intend to install the
PCIe card. Note: In single-processor systems,
PCIe slot 1 is nonfunctional; therefore, there
is no need to remove the filler panel for slot 1
There are three latching tabs on the sides of the cover, two on the right side and one on
Installation Procedure
1. Locate the vacant storage drive module slot
in the server, and then ensure that the release
lever on the filler panel is fully opened.
2. Slide the filler panel into the vacant slot
by pressing the middle of the filler panel
faceplate with your thumb or finger.
3. The release lever will close as it makes
contact with the chassis. Do not slide the
filler panel in all the way. Leave the filler
panel out approximately 0.25 to 0.50 inch (6
to 12 mm) from the opening.
4. Using your thumb or finger, press on the
middle of the filler panel faceplate until the
release lever engages with the chassis.
5. Close the release lever until it clicks into
place and is flush with the front of the server
1. Remove the server top cover.
2. To install the PCIe slot filler panel, press the
PCIe filler panel into the vacant PCIe slot,
and then rotate the PCIe locking mechanism
to secure the PCIe slot filler panel. Note:
In single-processor systems, PCIe slot 1 is
nonfunctional; therefore, the server ships
with this filler panel installed.