4-2 Wiring
Main Circuit and Motor Connections
When wiring the main circuit, use proper wire sizes, grounding systems, and noise resistance.
R88D-KNA5L-ML2/-KN01L-ML2/-KN02L-ML2/-KN04L-ML2/-KN01H-ML2/
-KN02H-ML2/-KN04H-ML2/-KN08H-ML2/-KN10H-ML2/-KN15H-ML2
Main Circuit Connector Specifications (CNA)
Symbol
4
L1
L2
L3
L1C
L2C
Motor Connector Specifications (CNB)
Symbol
B1
B2
B3
W
4-13
Name
Main circuit power supply
input
Control circuit power
supply input
Name
External Regeneration
Resistor connection
terminals
U
V
Motor connection
terminals
Frame ground
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
R88D-KNxL-ML2
(50 to 400 W) : Single-phase 100 to 120 VAC (85 to 127 V) 50/60 Hz
(200 to 400 W): 3-phase 100 to 120 VAC (85 to 127 V) 50/60 Hz
R88D-KNxH-ML2
(100 W to 1.5 kW) : Single-phase 200 to 240 VAC (170 to 264 V)
50/60 Hz
(100 W to 1.5 kW): 3-phase 200 to 240 VAC (170 to 264 V) 50/60
Hz
R88D-KNxL-ML2 :
Single-phase 100 to 120 VAC (85 to 132 V) 50/60Hz
R88D-KNxH-ML2 :
Single-phase 200 to 240 VAC (170 to 264 V) 50/60 Hz
50 to 400 W: These terminals normally do not need to be connected. If there
is high regenerative energy, connect an External Regeneration Resistor
between B1 and B2.
750 W to 1.5 kW: Normally B2 and B3 are shorted. If there is high
regenerative energy, remove the short-circuit bar between B2 and B3 and
connect an External Regeneration Resistor between B1 and B2.
Red
These are the output terminals to the Servomotor.
Be sure to wire them correctly.
White
Blue
Green/
Yellow
This is the ground terminal. Ground to 100 or less.