6-2 Forward and Reverse Drive Prohibition Functions
When the forward drive prohibition input (POT) and the reverse drive prohibition input (NOT)
are turned OFF, the motor stops rotating.
You can stop the motor from rotating beyond the device's operating range by connecting limit
inputs.
Parameters Requiring Settings
Parameter
number
Pn400 to
Input Signal Selection 1
Pn407
to 8
Pn504
Drive Prohibition Input
Selection
Pn505
Stop Selection for Drive
Prohibition Input
Pn511
Emergency Stop Torque
Pn710
MECHATROLINK-II
Communications I/O
Monitor Setting
Input Signal Selection Function (Default setting: Pn401, Pn402)
In the default setting, the allocations are as follows.
Parameter
number
Pn401
Pn402
Refer to "6-1 Sequence I/O Signal" (P.6-1) for details on input signal selections 1 to 8.
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
6-2 Forward and Reverse Drive Prohibition Functions
Parameter name
Set the input signal allocation and logic.
Set the operation to be performed upon forward
and reverse drive prohibition input.
Set the deceleration and stop methods upon
forward and reverse drive prohibition input.
Set the torque limit for an emergency stop.
Select whether to reflect the input to the
MECHATROLINK-II communications I/O
monitor, when either the Forward Drive
Prohibition Input or the Reverse Drive
Prohibition Input is allocated to the input signal,
and the Drive Prohibition Input Selection is set to
disabled (Pn504=1).
Parameter
name
Set value
Input Signal
00818181
Selection 2
Input Signal
00828282
Selection 3
Explanation
Default setting
Position Control
or full closing
Speed control
control
POT (NC)
POT (NC)
NOT (NC)
NOT (NC)
Reference
P.8-31
P.8-42
P.8-43
P.8-47
6
P.8-61
Torque
control
POT (NC)
NOT (NC)
6-6