Connecting an External Regeneration Resistor
R88D-KNA5L-ML2/-KN01L-ML2/-KN02L-ML2/-KN01H-ML2/-KN02H-ML2/-KN04H-ML2
Normally B2 and B3 are open.
If an External Regeneration Resistor is necessary, connect the External Regeneration Resistor
between B1 and B2 as shown in the diagram below.
Servo Drive
Precautions for Correct Use
Connect the thermal switch output so that the main circuit power supply is shut OFF when the
contacts open.
When using multiple External Regeneration Resistors, connect each thermal switch in series.
The resistor may be damaged by burning, or cause fire if it is used without setting up a power
supply shutoff sequence using the output from the thermal switch.
R88D-KN04L-ML2/-KN08H-ML2/-KN10H-ML2/-KN15H-ML2/-KN20H-ML2/-KN30H-ML2/
-KN50H-ML2/-KN06F-ML2/-KN10F-ML2/-KN15F-ML2/-KN20F-ML2/-KN30F-ML2/-KN50F-ML2
Normally B2 and B3 are short-circuited.
If an External Regeneration Resistor is necessary, remove the short-circuit bar between B2
and B3, and then connect the External Regeneration Resistor between B1 and B2 as shown
in the diagram below.
Servo Drive
Precautions for Correct Use
Connect the thermal switch output so that the main circuit power supply is shut OFF when the
contacts open.
When using multiple External Regeneration Resistors, connect each thermal switch in series.
The resistor may be damaged by burning, or cause fire if it is used without setting up a power
supply shutoff sequence using the output from the thermal switch.
OMNUC G5-Series AC Servo Drives Users Manual (Built-in MECHATROLINK-II communications type)
θ >
Thermal switch output
B1
External Regeneration Resistor
B3
B2
θ >
B1
B3
B2
Remove the short-circuit bar between B2 and B3.
4-4 Regenerative Energy Absorption
Thermal switch output
External Regeneration Resistor