Section 5
5.1
615 series ANSI
Engineering Manual
Protection and control engineering

Application Configuration tool

Application Configuration tool is used to modify an application configuration for a
protection relay and is based on IEC 61131-3 Function Block Diagrams.
The function blocks are dedicated to different functions.
Control related functions
Protection related functions
Monitoring functions
Communication
For more information on the function blocks, see the technical manual.
Most function blocks are mapped as logical nodes according to the IEC 61850 standard.
See the IEC 61850 parameter list for more information.
If a function block is removed with Application Configuration, the
function related data disappears from the menus as well as from the IEC
61850 data model, with the exception of some basic function blocks,
which are mandatory and thus cannot be removed from the relay
configuration by removing them from the Application Configuration.
Other function blocks are not mapped as logical nodes; for example, logical gates.
The basic features of Application Configuration tool include the ability to organize a
configuration into several MainApplications as well as providing different application
programming features.
Organize an application configuration
Organize an application configuration into a number of logical parts
(MainApplication)
Organize a MainApplication over a number of pages
Features for programming an application configuration
Protection and control engineering