Section 3
Interoperability profile for 615 series IEC 60870-5-103
3.3
3.3.1
3.3.2
3.3.3
3.3.3.1
3.3.3.2
22
Application layer
Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
COMMON ADDRESS of ASDU
⊠ One COMMON ADDRESS OF ASDU (identical with station address)
⃞ More than one COMMON ADDRESS OF ASDU
Selection of standard information numbers in monitor
direction
System functions in monitor directions
INF
Semantics
⊠
<0>
End of general interrogation
⊠
<0>
Time synchronization
⊠
<2>
Reset FCB
⊠
<3>
Reset CU
⊠
<4>
Start/restart
⊠
<5>
Power on
Status indications in monitor direction
INF
Semantics
⊠
<16>
Auto-recloser active 1
⃞
<17>
Teleprotection active
⃞
<18>
Protection active
⃞
<19>
LED reset
⃞
<20>
Monitor direction blocked
⊠
<21>
Test mode
⃞
<22>
Local parameter setting
⊠
<23>
Characteristic 1
⊠
<24>
Characteristic 2
⊠
<25>
Characteristic 3
⊠
<26>
Characteristic 4
Table continues on next page
1MRS756882 B
REM615
Point List Manual