Measured value expander block RANGE_XP

9.3.1

Identification

Function description
Measured value expander block
9.3.2

Application

The IEC 61850 generic communication I/O functions (MVGAPC) are provided with
measurement supervision functionality. All measured values can be supervised with four
settable limits, that is low-low limit, low limit, high limit and high-high limit. The measure value
expander block ( RANGE_XP) has been introduced to be able to translate the integer output
signal from the measuring functions to 5 binary signals, that is below low-low limit, below low
limit, normal, above high-high limit or above high limit. The output signals can be used as
conditions in the configurable logic.
9.3.3

Setting guidelines

There are no settable parameters for the measured value expander block function.
9.4

Parameter setting groups

9.4.1
Application
Six sets of settings are available to optimize IED operation for different power system
conditions. By creating and switching between fine tuned setting sets from the configurable
binary inputs, results in a highly adaptable IED that can cope with a variety of power system
scenarios.
Different conditions in networks with different voltage levels require highly adaptable
protection and control units to best provide for dependability, security and selectivity
requirements. Protection units operate with a higher degree of availability, especially, if the
setting values of their parameters are continuously optimized according to the conditions in
the power system.
Switchgear control unit SAM600-IO
Application manual
1
is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware
added to the product
3 is the Major revision of the manufactured product this means, functions or hardware is either
changed or enhanced in the product
Main function type code is present but not used because there is no IEC 60870-5-103
protocol in SAM600-IO.
© Copyright 2017 ABB. All rights reserved
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
Section 9
Basic IED functions
SEMOD52451-1 v2
SEMOD113212-2 v3
ANSI/IEEE C37.2
device number
-
SEMOD52434-4 v6
SEMOD113223-4 v1
M12007-6 v10
IP1745-1 v1
69