Section 3 Configuration; Communication Settings - ABB LD 800HSE Manual

Table of Contents

Advertisement

Section 3 Configuration

Communication Settings

Although the linking device is delivered with a pre-configured IP address
(192.168.1.20), it must be assigned an IP address from your LAN address range.
Furthermore, subnet mask and gateway IP address must be set accordingly. This
information is referred to as IP configuration.
Table 10
Table 10. Pre-configured IP Settings
Parameter Name
Host Name
IP Address
Subnet Mask
Maintenance IP
Address
Broadcast Address
Default Gateway
The IP configuration can be changed using one of the following methods:
3BDD011677-600 A
shows the pre-configured IP settings of the linking device.
Pre-configured value
LD 800HSE
192.168.1.20
255.255.255.0
192.168.1.21
192.168.1.255
192.168.1.21
Section 3 Configuration
Communication Settings
Remark
not used; you may leave this
unchanged or empty
mandatory
mandatory
recommended; for details
see
Network Configuration
on page 61
not used; it is automatically
adapted to the configured IP
address and subnet mask
it is not necessary to config-
ure a default gateway, if the
host and the linking device
share the same network
47