Introduction

There are four different software alternatives with which the IED can be ordered. The intention
is that these configurations shall suit most applications with minor or no changes. The few
changes required on binary input and outputs can be done from the signal matrix tool in the
PCM600 engineering platform.
The main protection functions are switched
generally used are also set to
The configurations are:
Single-breaker arrangement. Three-phase tripping arrangement.
Single breaker arrangement. Single-phase tripping arrangement.
Multi breaker arrangement. Three-phase tripping arrangement.
Multi breaker arrangement. Single-phase tripping arrangement.
The Multi-breaker arrangement includes one-and-a-half and ring-breaker arrangements.
The number of IO must be ordered to the application where more IO is foreseen for the single-
phase tripping arrangements respectively the multi-breaker arrangement.
The basic delivery includes one binary input module and one binary output module, which is
sufficient for the default configured IO to trip and close circuit breaker.
All IEDs can be reconfigured with the help of the ACT configuration tool in the PCM600
engineering platform. The IED can be adapted to special applications and special logic can be
developed, such as logic for automatic opening of disconnectors and closing of ring bays,
automatic load transfer from one busbar to the other, and so on.
On request, ABB is available to support the re-configuration work, either directly or to do the
design checking.
Optional functions and optional IO ordered will not be configured at delivery. It should be
noted that the standard only includes one binary input and one binary output module and only
the key functions such as tripping are connected to the outputs. The required total IO must be
calculated and specified at ordering.
Hardware modules are configured with the hardware configuration tool in the PCM600
engineering platform.
The application configuration tool, which is part of the PCM600 engineering platform, will
further to the four arrangements above include also alternatives for each of them with all of
the software options configured. These can then be used directly or as assistance of how to
configure the options. As the number of options can vary all alternatives possible cannot be
handled.
The configurations are as far as found necessary provided with application comments to
explain why the signals have been connected in the special way. This is of course for the
special application features created, not "standard" functionality.
Application configuration diagrams and connection diagrams for the maximum application
can be found in separate document, refer to section
Application manual