4.5: Voltage and Power Supply Connections

Voltage Inputs are connected to the back of the unit via a optional wire connectors. The connectors
accomodate up to AWG#12 / 2.5mm wire.
Power
Supply
Inputs
Voltage
Inputs

4.6: Ground Connections

The meter's Ground Terminals ( ) should be connected directly to the installation's protective earth
ground. Use 2.5mm wire for this connection.

4.7: Voltage Fuses

EIG recommends the use of fuses on each of the sense voltages and on the control power, even
though the wiring diagrams in this chapter do not show them.
Use a 0.1 Amp fuse on each voltage input.
Use a 3 Amp fuse on the power supply.
e
Electro Industries/GaugeTech
Figure 4.4: Voltage Connection
Doc # E145701
RS-485 Output
(Do not put the
Voltage on these
terminals!)
4-5