Compliance; Accuracy - Electro Industries Shark 100S Installation & Operation Manual

Electronic submeter with wifi ethernet capability
Hide thumbs Also See for Shark 100S:
Table of Contents

Advertisement

2.3: Compliance

• IEC 62053-22 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
• ANSI (IEEE) C37.90.1 Surge Withstand
• ANSI C62.41 (Burst)
• IEC1000-4-2: ESD
• IEC1000-4-3: Radiated Immunity
• IEC1000-4-4: Fast Transient
• IEC1000-4-5: Surge Immunity
• UL Listed
• CE Compliant

2.4: Accuracy

o
For 23
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A
(Class 10) nominal unit:
Parameter
Voltage L-N [V]
Voltage L-L [V]
Current Phase [A]
Current Neutral (calculated)
[A]
Active Power Total [W]
Active Energy Total [Wh]
Reactive Power Total [VAR] 0.2% of reading
Reactive Energy Total
[VARh]
Apparent Power Total [VA]
Electro Industries/GaugeTech
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The Leader In Power Monitoring and Smart Grid Solutions
Accuracy
2
0.1% of reading
0.1% of reading
1
0.1% of reading
1
2.0% of Full Scale
1,2
0.2% of reading
1,2
0.2% of reading
1,2
1,2
0.2% of reading
1,2
0.2% of reading
Doc
#
2: Meter Overview and Specifications
Accuracy Input Range
(69 to 480)V
(120 to 600)V
(0.15 to 5)A
(0.15 to 5)A @ (45 to 65)Hz
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
(0.15 to 5)A @ (69 to 480)V
@ +/- (0 to 0.8) lag/lead PF
(0.15 to 5)A @ (69 to 480)V
@ +/- (0 to 0.8) lag/lead PF
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
E145721
2 - 10

Advertisement

Table of Contents
loading