Display Configuration - Electro Industries Shark 200 Installation & Operation Manual

Low-cost high performance multifunction electricity meter
Hide thumbs Also See for Shark 200:
Table of Contents

Advertisement

Display Configuration
The settings on this screen determine the display
configuration of the meter's faceplate.
The screen fields and acceptable entries are as
follows:
Phases Displayed: A; A and B; A, B, and C.
This field determines which phases display on
the faceplate.
Auto Scroll Display: Yes or No. This field
enables or disables the scrolling of selected
readings on the faceplate. If enabled, the readings
scroll every 5 seconds.
Enable on Face Plate of Display: Check the boxes
of the Readings you want displayed on the faceplate of the meter.
You must select at least one reading.
Power Direction: View as Load or View as Generator
Flip Power Factor Sign: Yes or No.
®
NOTE: For a Shark
200T transducer, the Display Configuration does not apply as there is no display.
Energy, Power Scaling, and Averaging
The screen fields and acceptable entries
are as follows:
Energy Settings
Energy Digits: 5; 6; 7; 8
Energy Decimal Places: 0 - 6
Energy Scale: unit; kilo (K); Mega (M)
For Example: a reading for Digits: 8;
Decimals: 3; Scale: K would be formatted:
00123.456k
Power Settings:
Power Scale: Auto; unit; kilo (K); Mega (M)
Apparent Power (VA) Calculation Method:
Arithmetic Sum; Vector Sum
Demand Averaging:
Type: Block or Rolling
Interval (Block demand) or Sub-Interval (Rolling demand) in minutes: 5; 15; 30; 60
Number of Subintervals: 1; 2; 3; 4
Interval Window: This field is display only. It is the product of the values entered in the Sub-Interval and Number
of Subintervals fields.
NOTE: You will only see the Number of Subintervals and Interval Window fields if you select Rolling Demand.
5-9
e
Electro Industries/Gauge Tech
Doc# E149701