Digital Dry Contact Relay Output (Form C) Module; 1: Overview - Electro Industries Nexus 1262 Installation & Operation Manual

Billing meters
Table of Contents

Advertisement

10.6: Digital Dry Contact Relay Output (Form C) Module

Digital Dry Contact Relay Output (Form C) Module Specifications
Model Number
Accuracy
Scaling
Communication
Power Requirement
Operating Temperature
Maximum Load Impedance
Factory Settings
Default Settings
(Reset Button)

10.6.1: Overview

The Relay Output Module consists of four Latching Relay Outputs. In Normal Mode, the device
accepts commands to control the relays. Relay output modules are triggered by limits programmed
with the Communicator EXT software. See the Communicator EXT User Manual for details on
programming limits.
The Nexus® 1262/1272 unit does not supply power for the Relay Output modules. A power source
is required. See Section 10.2 for power and communication details.
The Modbus Map for the Relay Output Module (and operating details) can be found in the Modbus
Communicating Output Modules Manual.
Each latching relay will hold its state in the event of a power loss.
Electro Industries/GaugeTech
4RO1: 4 Latching Relay Outputs
0.1% of Full Scale
Programmable
RS485, Modbus RTU
Programmable Baud Rates: 4800, 9600, 19200, 57600
15–20V dc at 50–200 mA;
®
Nexus
1262/1272 Unit's Power Supply
DOES NOT Support Output Modules
(-20 to 79)°C / (-4 to +158)°F
0-1mA: 10k Ω;
Modbus Address: 156
Baud Rate: 57600
Transmit Delay Time: 0
Modbus Address: 247
Baud Rate: 57600
Transmit Delay Time: 20 csec
Doc # E151701
4-20mA: 500 Ω
10-9