4.2: CT Leads Terminated to Meter
®
The Shark
200 meter is designed to have Current Inputs wired in one of three ways. Diagram 4.1 shows the most
typical connection where CT Leads are terminated to the meter at the Current Gills. This connection uses Nickel-
Plated Brass Studs (Current Gills) with screws at each end. This connection allows the CT wires to be terminated us-
ing either an "O" or a "U" lug. Tighten the screws with a #2 Phillips screwdriver. The maximum installation torque
is 1 Newton-Meter.
Other current connections are shown in Figures 4.2 and 4.3. Voltage and RS485/KYZ Connection is shown in
Figure 4.4.
Current Gills
(Nickel-Plated Brass Stud)
Wiring Diagrams are shown in section 4.8 of this chapter.
Communications Connections are detailed in Chapter 5.
e
Electro Industries/Gauge Tech
Figure 4.1: CT Leads terminated to Meter, #8 Screw for Lug Connection
Doc# E149701