7.9: 10/100BaseT Ethernet Communication Card (INP100S)
The 10/100BaseT Ethernet Communication card provides the Shark® 200 meter with Ethernet capability. See
Chapter 8 for details and instructions.
NOTE: Refer to Chapter 5 of the Communicator EXT User's Manual for instructions on performing Network
configuration.
7.9.1: Specifications
The technical specifications at 25 °C are as follows:
Number of Ports:
Power consumption:
Baud rate:
Diagnostic feature:
Number of simultaneous Modbus
connections:
The general specifications are as follows:
Operating Temperature:
Storage Temperature:
Relative air humidity:
EMC - Immunity Interference:
Weight:
Dimensions (inch) W x H x L:
Connection Type:

7.9.2: Default Configuration

The Shark ® 200 meter automatically recognizes the installed option card during Power Up. If you have not
programmed a configuration for the card, the unit will default to the following:
IP Address: 10.0.0.2
Subnet Mask: 255.255.255.0
Default Gateway: 0.0.0.0
e
Electro Industries/Gauge Tech
1
2.1W internal
10/100Mbit
Status LEDs for LINK and ACTIVE
12
(-20 to +70) °C
(-40 to +80) °C
Maximum 95%, non-condensing
EN61000-4-2
1.7oz
0.72 x 2.68 x 3.26
RJ45 modular (Auto-detecting transmit and receive)