7.3.3.4: Configure PT Setting

Push the DOWN Button to scroll all the parameters in Configuration Mode: Scroll, CT, PT,
Connection (Cnct) and Port. The 'Active" parameter is in the A Screen and is flashing.
Push ENTER when PT is the 'Active' parameter and the Pt-n (Numerator) screen appears.
Push ENTER and the screen changes to Pt-d (Denominator).
ENTER again changes the screen to Pt-S (Scaling). The Pt-S setting can be '1', '10' or '100'.
To program any of these settings, see section 7.3.3.2 above.
Example Settings:
277/277 Volts:
14,400/120 Volts:
138,000/69 Volts:
345,000/115 Volts:
345,000/69Volts:
Push ENTER and the screen scrolls through the other CFG parameters.
Push DOWN or RIGHT and the Password screen appears (see section 7.3.2.1).
Push MENU and you will return to the MAIN MENU.
NOTE:
Pt-n and Pt-S are dictated by Primary Voltage.
Pt-d is Secondary Voltage.
e
Electro Industries/GaugeTech
Pt-n value is 277, Pt-d value is 277, Pt-Multiplier is 1.
Pt-n value is 1440, Pt-d value is 120, Pt-S value is 10.
Pt-n value is 1380, Pt-d value is 69, Pt-S value is 100.
Pt-n value is 3450, Pt-d value is 115, Pt-S value is 100.
Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000.
Doc # E145701
7-7