Step
6.
Switch module troubleshooting table
Step
1
2
11-10
Symptom
Possible Cause
-
Server blade
Table 11-5 Switch module troubleshooting table
Symptom
Possible Cause
•
A switch
•
No power.
module
•
Loose
does not
connection.
power
•
Damaged
up.
connector.
•
The
Power
LED is
off.
The Status
•
Bios boot
LED lights in
failure.
red.
•
Any failure
detects by
software.
Troubleshooting
Hitachi Compute Blade 500 Series System Service Manual
Actions / Verifications
1
Press the Power switch to power on the
.
suspected server blade.
Verification 2
1
If the Power LED is solid green, Error/
.
Fault LEDs are off and power up is
successful, then repair is completed.
2
If the symptom still exists, then go to
.
step 6.
Action 1
1
Contact with Hitachi Data Systems
.
technical support. See the Getting help
section in this manual.
Actions / Verifications
Action 1
1
Remove the suspected switch module.
.
2
Inspect the connector for damage.
.
3
Install it into the original bay again if it did
.
not have damaged connector.
Verification 1
1
If the Power LED of the suspected switch
.
module lights on green, the repair is
completed.
2
If the suspected switch module has
.
damaged connector, then go to step 5.
3
If the Power LED remains off, go to Action
.
2.
Action 2
1
Remove the suspected switch module and
.
replace it with the spare one.
Verification 2
1
If the Power LED lights on green, replacing
.
is completed.
2
If the Power LED remains off, go to step 4.
.
Action 1
1
Remove the suspected switch module.
.
2
Inspect the connector for damage.
.
3
Install it into the original bay again if it did
.
not have damaged connector.
Verification 1