Replacing A Management Module (Non-Redundant); Removing A Management Module - Hitachi CB 520H B1 Service Manual

Compute blade 500 series
Hide thumbs Also See for CB 520H B1:
Table of Contents

Advertisement

26
Verify that the power LED lights in green after blinking, and that the
.
primary LED is off.
27
Set up TOD if you need.
.
See
28
Verify that the replacement was successful through the MAR log.
.
See
29
Turn off the maintenance mode from web console.
.
See

Replacing a management module (non-redundant)

This procedure describes how to replace a management module under the
non-redundant configuration. Under this configuration, the single
management module is installed in chassis.

Removing a management module

1
Put on an anti-static wrist strap.
.
2
Connect web console. See
.
section.
3
Turn on LID LED for identifying the target module.
.
See
4
Turn on the maintenance mode from web console.
.
See
5
Identify F/W version and take notes of it.
.
See
6
Back up the configuration data to the USB memory in the front panel or
.
any storage in the local PC. See
section.
7
Select Resources tab on the web console and select System > Network
.
> Internal LAN.
8
Confirm IP address and Subnet mask.
.
5-106
Time of Day (TOD) clock setup procedure on page 4-44
Alert information identification procedure on page 4-5
Maintenance mode on/off procedure on page 4-10
Identify LED (LID) on/off procedure on page 4-7
Maintenance mode on/off procedure on page 4-10
F/W version identification procedure on page 4-22
Replacing parts
Hitachi Compute Blade 500 Series System Service Manual
Web console login procedure on page 4-3
Backup/restore procedure on page 4-30
section.
section.
section.
section.
section.
section.