Step
2.
3.
11-8
Symptom
Possible Cause
A server
Configuration
blade does
Error
not power
up.
Power LED:
Blink.
Error LED:
On
Fault LED:
Off
A server
Hardware Error
blade does
not power
up.
Power LED:
Blink.
Error LED:
On
Fault LED:
On
Troubleshooting
Hitachi Compute Blade 500 Series System Service Manual
Actions / Verifications
Action 2
1
Press the power switch to power on the
.
suspected server blade.
Verification 2
1
If the Power LED is solid green, then the
.
repair is completed.
2
If the symptom still exists, then go to
.
step 6.
Action 1
1
Verify the Error Status through the web
.
console.
2
Remove the suspected server blade.
.
3
Inspect the connector for damage.
.
4
Review the type and position of each
.
component (Processor, DIMM and
Mezzanine card).
5
Install it into the original bay again if it
.
did not have damaged connector.
Verification 1
1
If the Power LED starts blink in green and
.
Error/Fault LEDs are off, go to Action 2.
2
If the suspected server blade has
.
damaged connector, then go to step 6
3
If the symptom still exists, then go to
.
step 6.
Action 2
1
Press the power switch to power on the
.
suspected server blade.
Verification 2
1
If the Power LED is solid green, Error/
.
Fault LEDs are off, and power up is
successful, then repair is completed.
2
If the symptom still exists, then go to
.
step 6.
Action 1
1
Verify the Error Status through the web
.
console.
2
Remove the suspected server blade.
.
3
Replace the suspected component(s)
.
identified by the web console.
4
Install it into the original bay again.
.
Verification 1
1
If the Power LED starts blink in green and
.
Error/Fault LEDs are off, go to Action 2.
2
If the suspected server blade has
.
damaged connector, then go to step 6