Remove a Power Supply

Legend
1
2
Related Information
"Remove a Power Supply" on page 70
"Install a Power Supply" on page 72
Remove a Power Supply
This is a hot-service procedure that can be performed by a customer while the server is running.
Caution -
personal health, follow the instructions.
Caution -
airflow, leave the failed power supply installed in the server until you replace it with a new
power supply.
1.
Identify which power supply requires replacement.
Locate the power supply with the lit amber Service Required LED.
You can also use the Oracle ILOM show faulty command at the Oracle ILOM
command line prompt (->) to identify a power supply failure.
2.
Gain access to the rear of the server where the faulty power supply is located.
If the CMA is installed, disconnect both CMA left-side connectors and move the
3.
CMA out of the way.
70
SPARC S7-2 Server Service Manual • March 2017
Status
Icon
Indicator
Name
AC OK/DC
OK
Service
Required
Hazardous voltages are present. To reduce the risk of electric shock and danger to
If a power supply fails and you do not have a replacement available, to ensure proper
Color
State Meaning
■ Off – No AC power is present.
Green
■ Slow blink – Normal operating. Input power is within
specification. DC output voltage is not enabled.
■ Steady on – Normal operation. Input AC power and DC
output voltage are within specification.
Amber
■ Off – Normal operation; no service required.
■ Steady on– The power supply (PS) has detected a PS fan
failure, PS overtemperature, PS over current, or PS over/
under voltage.