Input Signals
Signal
Function
IN0
Turn ON.
IN1 and IN2
Turn OFF.
IN3
Turn ON.
IN4 and IN5
Turn OFF.
IN6
Turn ON.
IN7
This signal is the trigger for executing teaching. Set the IN0 to IN6 signals, wait for at least 5 ms, and then turn
ON the IN7 signal. The BUSY signal will be ON while the command is being executed.
Clearing the OR and D Signals
This command clears the OR signal and D signals.
Parameters
Execution
Command
IN7
IN6
1
1000010
Timing Chart
Run Mode entered.
ON
RUN signal
OFF
ON
TRIG signal
OFF
ON
BUSY signal
OFF
ON
OR signal
OFF
D signals
ON
GATE signal
OFF
IN0 to IN6
signals
ON
IN7 signal
OFF
ON
ACK signal
OFF
82
Controlling Operation and Outputting Data with a Parallel Interface Sensor Data Unit
IN5
IN4
IN3
ON for 1 ms min.
TRIG is input.
Measurements executed.
Data
GATE ON delay
Output time
Allow 5 ms min.
and then turn ON IN7.
IN2
IN1
IN0
Setup Mode entered.
0
1000010
ON for 1 ms min.
ACK output time
Input example
11000010
FQ2-S/CH User's Manual
for Communications Settings