Nortel DMS-100 Series Replacement Procedures page 62

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-30 XPM card replacement procedures
NT0X10
in an RSC-S (DS-1) Model A RMM
9
10
11
12
13
14
297-8021-547 Standard 14.02 May 2001
Use the following information to determine what step to go to next in this
procedure.
If you entered this procedure
from
alarm clearing procedures
other
Send any faulty cards for repair according to local procedure.
Record the date the card was replaced, the serial number of the card, and the
symptoms prompted by replacement of the card. Go to step 14.
Return to the procedure that directed you to this procedure. At the point
where a faulty card list was produced, identify the next faulty card on the list
and go to the appropriate card replacement procedure for that card in this
manual.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
(end)
Do
step 12
step 10