Nortel DMS-100 Series Replacement Procedures page 36

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-4 XPM card replacement procedures
NT0X10
in an IOPAC RMM
Replacing an NT0X10 in an RMM
At the MAP
1
2
At the MAP terminal
3
4
297-8021-547 Standard 14.02 May 2001
(continued)
CAUTION
Loss of service
This procedure includes directions to manually busy one or
more peripheral module (PM) units. Since manually busying
a PM unit can cause service degradation, perform this
procedure only if necessary to restore out of service
components. Otherwise. carry out this procedure during
periods of low traffic.
Obtain a replacement card. Ensure the replacement card has the same
product equipment code (PEC), including suffix, as the card to be removed.
If you were directed to this procedure from the Alarm Clearing Procedures ,
go to step 5. Otherwise, continue with step 3.
Access the trunk test position (TTP) level and post the RMM that contains the
card to be replaced by typing
>MAPCI;MTC;TRKS;TTP;POST P RMM rmm_no ckt_no to ckt_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf where the card is to be replaced
ckt_no
is the number of the circuit associated with the card to be replaced
Ensure the correct circuit card is removed from the shelf by typing
>CKTLOC
and pressing the Enter key.