Avaya Definity SI Maintenance Manual page 1372

Table of Contents

Advertisement

Maintenance Object Repair Procedures
Table 10-217. DS1 DIOD Error Log Entries — Continued
Error
Aux
Type
Data
2305(k)
50944
2562(l)
16665
2817(m)
52992
3840(n)
Port Audit and
Update Test (#36)
1
Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
2
This alarm will only be raised when the System-Parameter Country form has the Base Tone
Generator field set to 4 (Italy). This alarm will be a MINOR alarm unless 75% or more trunks in this
trunk group are out of service, then the alarm will be upgraded to a MAJOR alarm.
3
Major alarms on this MO may be downgraded to Warning alarms based on the value used in the set
options command.
Notes:
a. Error Type 1—Aux Data 57408
call.
Aux Data 57476—Rotary Dial before Wink.
Aux Data 57477—Rotary Dial pulse too early.
Aux Data 57485—Wink too short for a valid signal.
Aux Data 57487—PBX could not get "loop close" signal
The DS1 Interface circuit pack detected a hardware fault. These errors will
cause the Dial Tone Test (#314) to run and are only considered a problem if
the Dial Tone Test fails (in which case Error Type 1025 will also show up).
In this case, the trunk may be put in the ready-for-service state (shown as
"disconnected" by the status command), which allows only incoming calls.
Run the Dial Tone Test (#314) and follow the procedures.
b. Error Type 15—This is a software audit error that does not indicate any
hardware malfunction. Run Short Test Sequence and investigate
associated errors (if any).
c. Error Type 18—System Technician has busied out the trunk to the
out-of-service state. No calls can be made on this trunk except the Facility
Access Test Call. For details on this feature, refer to "Facility Test Calls"
section in Chapter 5, "Routine Maintenance Procedures".
d. Error Type 130—This error type indicates that the circuit pack has been
removed or has been insane for more than 11 minutes. To clear the error,
reinsert or replace the circuit pack.
10-586
Issue 4 May 2002
Alarm
Associated Test
Level
On/Off
Board
Test to Clear Value
Continued on next page
No tip ground is detected on an outgoing
555-233-123