DS1-BD (DS1 Interface Circuit Pack)
Table 10-242. TEST #145 Misframe Alarm Inquiry Test
Error
Code
Test Result
ABORT
2100
ABORT
2000
ABORT
555-233-123
Description/Recommendation
Internal system error
Could not allocate the necessary system resources to run this
test.
1. Retry the command at 1-minute intervals a maximum of 5
times.
Response to the test was not received within the allowable
time period. This may be due to hyperactivity. Error type 1538
in the error log indicates hyperactivity. The hyperactive circuit
pack is out of service and one or more of the following
symptoms may appear.
1. The DS1-BD tests (such as test 138 and test 139) are
aborting with error code 2000.
2. The tests run on the ports of this circuit pack are returning
a no board result.
3. busyout and release have no affect on the test results.
4. A list config command shows that the circuit pack and the
ports are properly installed.
NOTE:
When hyperactivity occurs, the circuit pack is isolated
from the system, and all of the trunks for this circuit pack
are placed into the out of service state. The system will
try to restore the circuit pack within 15 minutes. When
no faults are detected for 15 minutes, the DS1 interface
circuit pack is restored to normal operation. All of the
trunks for the DS1 interface circuit pack are then
returned to the in service state. Hyperactivity is often
caused by the associated facility. In such a case, faults
(such as slips, misframes, or blue alarms) would be
entered in the error log. In addition, many hardware
errors would be logged against the associated trunk
circuits. If the facility is OK and the error occurs again
after 15 minutes, escalate this problem.
Continued on next page
Issue 4 May 2002
10-659