Generator- Fault Shutdowns
Always identify and correct the cause of a fault as shown
on the opposite page before resetting the controller at
the generator unit. When a fault shutdown occurs follow
this procedure to reset the controller.
1. Move the generator set master switch to the "OFF/
RESET" position.
2. Disconnect the generator unit from the load using the
line circuit breaker. The circuit breaker is located above
the digital controller at the generator unit. See the safety
warnings at the beginning of this chapter. Refer to illus-
tration A.
3. Identify and correct the cause of the fault shutdown.
See the safety warnings at the beginning of this chapter.
4. Start the generator set by moving the generator set
master switch to the "RUN" position. Test run the gen-
erator to make sure the fault has been corrected.
5. Shut the generator off by moving the generator set
master switch to the OFF/RESET position.
6. Reconnect the generator line to the load by turning on
the generator circuit breaker located above the digital
controller.
7. Move the generator set master switch to the AUTO
position for startup.
Equipment Operation
Generator
Circuit
Breaker
187