Configuring the fieldbus
7.3 Communication via PROFIBUS
7.3.4

Setting the address

You set the PROFIBUS address of the inverter using
the address switch on the Control Unit, using
parameter p0918 or in STARTER.
Using parameter p0918 (factory setting: 126) or using
STARTER, you can only set the address, if all
address switches are set to "OFF" (0) or "ON" (1).
If you have specified a valid address using the
address switches, this address will always be the one
that takes effect and parameter p0918 cannot be
changed.
Valid address range: 1 ... 125
The positions of the address switches are described
in Section: Overview of the interfaces (Page 56).
Procedure
To change the bus address, proceed as follows:
1. Set the address using one of the subsequently listed options:
– using the address switches
– with an operator panel using p0918
2. Switch on the inverter power supply and, if being used, the 24 V supply
for the Control Unit.
3. Switch on the voltages again after all LEDs at the inverter have gone dark.
This means that you have changed the bus address.
7.3.5
Select telegram – procedure
Precondition
In the basic commissioning, you have selected a setting with fieldbus.
See also Section: Selecting the pre-assignment for the terminal strip (Page 60).
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.
118
– in STARTER using screen form "Control Unit/Communication/PROFIBUS", or using
the expert list with p0918
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB