Inhibit Direction Of Rotation; Minimum Speed - Siemens SINAMICS G120 Operating Instructions Manual

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Setting functions
8.4 Setpoint calculation
8.4.3

Inhibit direction of rotation

In the factory setting of the inverter, both motor directions of rotation are enabled.
Procedure
Proceed as follows to permanently lock a direction of rotation:
Set the corresponding parameter to a value = 1.
You have permanently locked the appropriate direction of rotation.
Table 8- 16
Parameter
p1110 = 1
p1110 = 722.3
8.4.4

Minimum speed

Function
The converter prevents continuous motor operation
at speeds < minimum speed.
Speeds, where the absolute value is less than the
minimum speed, are only possible when
accelerating or braking.
Table 8- 17
Parameter
p1080
236
Examples of settings to inhibit the direction of rotation
Remark
Inhibit negative direction
Negative direction is permanently inhibited.
Inhibit negative direction
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Setting the minimum speed
Description
Minimum speed
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents