Siemens SINAMICS G120 Operating Instructions Manual page 333

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Procedure with safety functions:
To load the settings from the PG to the inverter and to activate the safety functions, proceed
as follows:
1. Go online with STARTER :
2. Select the button "Download project to target system":
3. Call the STARTER screen form for the safety functions.
You have transferred the settings from the PG to the inverter.
To activate the safety functions, proceed as follows:
1. Select the "Copy parameter" button.
2. Press the "Activate settings" button.
3. To save the data in the inverter, select the "Copy RAM to ROM" button:
4. Go offline with STARTER :
5. Switch off the inverter power supply.
6. Wait until all LED on the inverter go dark.
7. Switch on the inverter power supply again. Your settings only become effective after this
You have transferred the settings from the PG to the inverter and have activated the safety
functions.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB
power-on reset.
Backing up data and series commissioning
.
.
9.2 Saving settings on a PC
.
.
333