Configuring the fieldbus
7.5 PROFIenergy profile for PROFINET
Table 7- 10
Bit 0
0
1
0
0
Additional settings and displays
Settings
● Minimum pause time: p5602
is the time that the machine requires to change into the energy-saving mode and back
into the production mode.
● Maximum pause time: p5606
● Signal source to set the inverter into state S1 (switching on inhibited): p5614
(e.g. p5614 = 722.0, means that you bring the inverter into the "switching-on inhibited"
state via DI0).
● Reset the energy usage display to 0: p0040
142
Dependency on the settings of p5611.0 ... p5611.2
Bit 1
Bit 2
0
0
Energy-saving mode enabled.
Display in r5613
•
no additional "automatic" responses.
•
Set the responses to PROFIenergy commands on the inverter side.
•
0/1
0/1
Energy-saving mode not enabled. No response to PROFIenergy commands
from the control
1
0
Energy-saving mode enabled with the following responses:
Display in r5613
•
OFF1 is set if the "Start_Pause" command is received from the control.
•
–
The command is immediately effective in the inverter states "switching
on inhibited" (S1) or "ready to start" (S2).
–
In the "operation" state (S4), OFF1 only becomes effective if the
inverter has been brought into the "switching on inhibited" (S1) or
"ready to start" (S2) state as a result of other commands, either from
the control or inverter side.
The inverter cannot be switched on as long as the "Start_Pause" command
•
is present.
The OFF1 command is withdrawn with "End_Pause".
1
1
Energy-saving mode enabled with the following responses:
Display in r5613
•
OFF1 is set if the "Start_Pause" command is received from the control.
•
The command is immediately effective in the inverter states "switching on
inhibited" (S1), "ready to start" (S2), "ready" (S3) and operation (S4).
With the "End_Pause" command, the pulses are re-enabled and the motor
•
starts, if one of the states "ready" (S3) or "operation" (S4) is present.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB