Configuring the fieldbus
7.5 PROFIenergy profile for PROFINET
Table 7- 10
Bit 0
0
1
0
0
Additional settings and displays
Settings
● Minimum pause time: p5602
is the time that the machine requires to change into the energy-saving mode and back
into the production mode.
● Maximum pause time: p5606
● Signal source to set the inverter into state S1 (switching on inhibited): p5614
(e.g. p5614 = 722.0, means that you bring the inverter into the "switching-on inhibited"
state via DI0).
● Reset the energy usage display to 0: p0040
142
Dependency on the settings of p5611.0 ... p5611.2
Bit 1
Bit 2
0
0
Energy-saving mode enabled.
Display in r5613
no additional "automatic" responses.
Set the responses to PROFIenergy commands on the inverter side.
0/1
0/1
Energy-saving mode not enabled. No response to PROFIenergy commands
from the control
1
0
Energy-saving mode enabled with the following responses:
Display in r5613
OFF1 is set if the "Start_Pause" command is received from the control.
The command is immediately effective in the inverter states "switching
on inhibited" (S1) or "ready to start" (S2).
In the "operation" state (S4), OFF1 only becomes effective if the
inverter has been brought into the "switching on inhibited" (S1) or
"ready to start" (S2) state as a result of other commands, either from
the control or inverter side.
The inverter cannot be switched on as long as the "Start_Pause" command
is present.
The OFF1 command is withdrawn with "End_Pause".
1
1
Energy-saving mode enabled with the following responses:
Display in r5613
OFF1 is set if the "Start_Pause" command is received from the control.
The command is immediately effective in the inverter states "switching on
inhibited" (S1), "ready to start" (S2), "ready" (S3) and operation (S4).
With the "End_Pause" command, the pulses are re-enabled and the motor
starts, if one of the states "ready" (S3) or "operation" (S4) is present.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB