Error numbers for response identifier 7
Description
Illegal parameter number (access to a parameter that does not exist)
Parameter value cannot be changed (change request for a parameter value that cannot be
changed)
Lower or upper value limit exceeded (change request with a value outside the value limits)
Incorrect subindex (access to a subindex that does not exist.)
No array (access with a subindex to non-indexed parameters)
Incorrect data type (change request with a value that does not match the data type of the
parameter)
Setting not permitted, only resetting (change request with a value not equal to 0 without
permission)
Descriptive element cannot be changed (change request to a descriptive element error
value that cannot be changed)
No master control (change request but with no master control, see also p0927.)
Keyword missing
Request cannot be executed due to the operating state (access is not possible for
temporary reasons that are not specified)
Inadmissible value (change request with a value that is within the limits but which is illegal
for other permanent reasons, i.e. a parameter with defined individual values)
Parameter number is currently deactivated (depending on the mode of the inverter)
Channel width is insufficient (communication channel is too small for response)
Illegal parameter value (parameter can only assume certain values)
Request not included / task is not supported (the valid request identifications can be found
in table "Request identifications controller → inverter")
No change access for a controller that is enabled. (operating status of the inverter
prevents a parameter change)
Write access only for commissioning (p0010 = 15) (operating status of the inverter
prevents a parameter change)
Know-how protection active, access locked
Change request below the currently valid limit (change request to a value that lies within
the "absolute" limits, but is however below the currently valid lower limit)
Change request above the currently valid limit (example: a parameter value is too large for
the inverter power)
Change request not permitted (change is not permitted as the access code is not
available)
PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
PNU = parameter number - offset.
Write the parameter number minus the offset into the PNU
(PKE bit 10 ... 0).
Write the offset in the page index (IND bit 15 ... 8).
Configuring the fieldbus
7.7 Communication via RS485
163