Siemens SINAMICS G120 Operating Instructions Manual page 84

Inverter with the cu250s-2 control unit (vector)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Commissioning
5.3 Restoring the factory setting
Procedure
Proceed as follows to restore the safety function settings in the inverter to the factory
settings using STARTER:
1. Go online
2. Call the safety functions screen form
3. In the "Safety Integrated" screen form, press the button for restoring the factory setting.
4. Enter the correct password.
5. Switch off the inverter power supply.
6. Wait until all LEDs on the inverter go dark.
7. Switch on the inverter power supply again.
You have restored the safety function settings of your inverter to the factory settings using
STARTER.
Restoring the inverter to the factory setting
Procedure
Proceed as follows to restore the inverter settings to the factory settings using STARTER:
1. Go online
2. Click the
You have restored the inverter factory settings.
Proceed as follows to restore the inverter settings to the factory settings using the BOP-2:
1. In the "Options" menu, select the "DRVRESET" entry
2. Confirm the reset using the OK key
You have restored the inverter factory settings.
84
key.
Converter with the CU250S-2 Control Unit (vector)
Operating Instructions, 06/2013, FW V4.6, A5E31759476B AB